Selection criteria for gratings
|
feature |
Welded press grating (SP) |
Press grate (P) |
Insert grate (EP) |
|
Basic principle |
Load-bearing bars and crossbars are welded together at each node. |
Crossbars are pressed into the load-bearing bars (without welding). |
The load-bearing and crossbars are slotted and inserted into each other (positive locking). |
|
Connection of the rods |
Fabric-bonded (welded seam) |
Form-fit through pressing |
Form-fit connection via slotted joint |
|
Crossbars |
Mostly rectangular |
Usually slotted |
Slotted , interlocking |
|
Edge bars |
Available around the perimeter |
Available around the perimeter |
Available around the perimeter |
|
Stiffness |
Very high |
High |
Medium to high |
|
Torsional strength |
Very good |
Good |
Good |
|
Vibration behavior |
Small amount |
Medium |
Medium |
|
Corrosion protection after manufacturing |
Easily controllable |
Very good (no weld points in the grid) |
Good |
|
optics |
"Technical", weld points visible |
Clean raster image |
Very uniform grid |
|
Manufacturing costs |
Tendency higher |
Medium |
Medium |
|
dimensional accuracy |
Very precise |
Very precise |
Precise |
|
Repairability |
Easily repairable |
Restricted |
Restricted |
|
Typical use |
Industry, heavy loads |
Architecture + Industry |
Facades, sun protection, lightweight constructions |
Essential planning and selection criteria for gratings
When selecting the appropriate grating, in addition to the grating type , the load-bearing capacity, deflection, and fastening must be taken into account. The chosen grating must reliably and permanently meet the specific operating conditions.
The following points should be noted in particular:
- Types of stress:
- uniformly distributed surface loads (min. 2.0 kN/m²),
- stationary or rolling point loads (min. 1.5 kN on 200 × 200 mm),
- Static and dynamic loads (e.g., from people or vehicles).
- Load capacity:
- Selection based on manufacturer's load tables,
- Consideration of span, material and safety factors,
- Static calculations may need to be performed by a specialist engineer in special cases.
- Deflection:
- The elastic deflection should generally not exceed L/200 .
- At joints, the height difference to adjacent grates must not exceed 4 mm .
- Fastening and support:
- secure and permanent anchoring to the substructure,
- possibly additional supports or reinforced edge connections,
- Adjacent grates are connected by butt joints or double clamps.
- Operating conditions:
- Slip resistance,
- Corrosion protection,
- Temperature resistance
- Weather conditions and aggressive media.
Essential planning and selection criteria for gratings
- Clarify the load – consider area loads, point loads and static/dynamic loads.
- Select load-bearing capacity – based on manufacturer's tables (material, span, safety factors).
- Limit deflection – id R. max. L/200 , impact height difference ≤ 4 mm .
- Secure fastening – permanent anchoring to the substructure, possibly with additional supports.
- Secure rust connections – use butt joints or double clamps.
- Consider operating conditions – slip resistance, corrosion, temperature, weather/media.